(148d) Causes and Future Prevention of a Firebox Overpressure Event
AIChE Spring Meeting and Global Congress on Process Safety
2023
2023 Spring Meeting and 19th Global Congress on Process Safety
Topical 4: The 35th Ethylene Producers Conference
Ethylene Plant Safety
Wednesday, March 15, 2023 - 3:40pm to 4:05pm
During normal cracking operation of an ethylene furnace in one of Saudi Chevron Phillips plants, the induced draft inlet damper suddenly went to the closed state at full firing rate. There was no furnace trip for this condition by design. This led to high firebox pressure with hot flue gas coming out of the peep doors and resulted in damage to the firebox structure and surrounding instrument cabling and lighting. This paper will go through the details of the incident, the learnings from the incident investigation and some corrective actions implemented.