(67a) Caribbean Petroleum Explosion Case Study
AIChE Spring Meeting and Global Congress on Process Safety
2019
2019 Spring Meeting and 15th Global Congress on Process Safety
Global Congress on Process Safety
Fires, Explosions, and Reactive Chemicals I
Tuesday, April 2, 2019 - 8:00am to 8:30am
Caribbean Petroleum Explosion Case Study
Q.A. Baker, J.K. Thomas, D.R. Malik and M.T. Edel
Baker Engineering and Risk Consultants
3330 Oakwell Court, Suite 100
San Antonio, TX
78218-3024
(210) 824-5960
A vapor cloud explosion (VCE) occurred at the Caribbean
Petroleum site in Bayamón, Puerto Rico on October 23,
2009 shortly after midnight. An above-ground
gasoline storage tank (Tank 409) was being loaded from a cargo ship
shortly before the incident. Overfilling
of Tank 409 resulted in gasoline discharge through elevated tank vents and
the creation of a very large vapor-mist cloud, which extended off the plant site
into surrounding areas covered with heavy vegetation. Approximately 5,000 barrels (210,000 gallons,
790,000 liters) of gasoline were released, creating a cloud with a footprint of
roughly 3x106 ft2 (70 acres, 0.3 km2). The over-fill was halted roughly 10 minutes
prior to the VCE. The cloud was ignited
at an electrical equipment enclosure outside the electrically classified
area. The resulting VCE caused blast damage
to both on-site and off-site structures.
Fires were ignited in a number of other storage tanks within the tank
farm, which burned for several days.
Based on comparisons with the damage observed by the authors
both on- and off-site, it was concluded that the VCE preceded as a
deflagration, with vegetation located outside of the tank farm representing most
of the congestion responsible for the VCE.
The flammable cloud did not reach the congestion associated with the
adjacent decommissioned refinery process units; these congested areas therefore
did not participate in the VCE. The tank
farm itself is an area of relatively low congestion. Contrary to some reports in the literature,
which appear to have focused primarily on individual damage indicators within
the vapor cloud, the results of this investigation indicated that the VCE did
not precede as a detonation (i.e., a deflagration-to-detonation transition did
not occur). Additionally, contrary to
the findings of some of the other investigations of this incident, it was
concluded that the flame did not propagate through the east-west sewers.
This paper will present key findings from the investigation,
the basis for these findings, and the main lessons learned from this incident.
Checkout
This paper has an Extended Abstract file available; you must purchase the conference proceedings to access it.
Do you already own this?
Log In for instructions on accessing this content.
Pricing
Individuals
AIChE Pro Members | $150.00 |
Employees of CCPS Member Companies | $150.00 |
AIChE Graduate Student Members | Free |
AIChE Undergraduate Student Members | Free |
AIChE Explorer Members | $225.00 |
Non-Members | $225.00 |